UPS Systems, Custom Built Industrial UPS, UPS Accessories, Telecom Inverter, Solar PCU, Frequency Converter, Static Transfer Switches, Digital Active Power Conditioner

Quick Links
 
 
 
 
 
 
 
 
 
 
 
 
 
Hux 110
Specifications
 
 
  • DSP controlled system
  • Near unity Power Factor (>0.95)
  • Smaller foot print area
  • Intelligent battery charging management
  • Advanced communication - RS 232, SNMP compatible
Products Range
UPS Systems
     HNux 110
     LNux 110
     LN 3100 / 3300
 
Contact Us
M/S. SYSCON ENTERPRISES,
Flat No. 2, D Building, Garuda Heritage, behind Panjab National Bank, Aundh,
Pune- 411 007, MH, India
Tel. No. : +91 - 20 - 65233381, 27297031 / 32 / 33
Fax : +91 - 20 - 27297033,
Mobile : +91 - 93710 24941, 98220 56147, 9011049056, 90110 49057
E-mail : sysconpune@vsnl.com / a_karnalkar@sysconpune.com
 
 
 
 
 
 
 
Model
HNux 110 S4
HNux 110 S4
HNux 110 S5
Rating
1 kVA
3 kVA
6 kVA
Input Voltage
230 VAC (160 - 300 V) 1 ph
230 VAC ( 176 - 276 V ) 1 Ph
Input Frequency
50 Hz (47.5 to 52.5 Hz )± 5%
50 Hz (46 to 54 Hz ) ± 8%
Input Power Factor
≥ 0.95
≥ 0.97
≥ 0.98
Battery Voltage
36 VDC
96 VDC
240 VDC
Output Power
1 kVA @ 0.7 pf
3 kVA @ 0.7 pf
6 kVA @ 0.7pf
Output Voltage
230 V AC ( 220 / 240 V Adjustable ) (± 2 %) 1 Ph
230 V AC ( 220 / 240 V Adjustable ) ( ± 1 %) ph
Waveform
True Sine Wave
Output Frequency
50 Hz ( ± 0.2 Hz ) Battery mode
( ± Hz ) in synchronous mode
50 Hz ( ± 0.5 Hz ) Battery mode
( ± 4 Hz ) in sychronous mode
Total Harmonic Distortion
≤ 3% max. for 100% Linear load
≤ 2% max. for 100% Linear load
Crest Factory
3:1
Overload Capacity (Mains )
105 tp 150% to 30 Sec
> 150 % for 200 ms
105 to 130 % for 10 min
> 130 % for 1 Sec. (transfers to bypass)
Acoustic Noise Level
≤ 41 dBA @ 1.0 meter
≤ 50 dBA @ 1.0 meter
≤ 55 dBA @ 1.0 meter
Automatic Bypass
Integrated Standard Static Bypass
Cooling
Forced Air
Relative Humidity
20 to 90% ( non condensing )
Dimensions WxDXH (in mm)
148 x 400 x 222
195 x 465 x 345
260 x 717 x 570
Weight (Approx)
7.5 kg
16 kg
35 kg
LED Indications

Fault, Load Bar graph, Battery Capacity bar graph, Load on bypass, Mains ON, Inverter ON, Battery Mode

LCD Display
.
.

% Load, Input Frequency, Input Voltage, Output Voltage, Output Frequency, Bypass Active, Batterey Voltage, Battery Capacity %, Fault

 
Home | Profile | Products | UPS | HNux 110 | LNux 110 | HN 110, 310 | LN 3100 / 3300
| Swan Digital Active Power Conditioner | Clients | Contact Us | Feedback
Designed by : MID   Hosted by : GID   Promoted by : PBD